FaultCodes.org
F5ViessmannAir Pressure Switch & FlueVerified Guide· Updated: Nov 22, 2026

Viessmann Boiler Fault F5 (F05): Air Pressure Switch / Flue Draft Error

Combustion safety lockout when the differential air pressure switch fails to open before blower start or close under differential pressure (Pa)—check outside flue outlet safely, try one reset, then call a certified heating engineer.

Quick AnswerCritical — Stop Immediately

Fault code F5 (also shown as F05) on Viessmann Vitopend and fan-flued Vitodens boilers indicates an *air pressure switch (`Prosestat` / Differenzdruckwächter) fault: the switch either stayed stuck closed before fan startup or failed to close once the fan ran because differential pressure (Pa) wasn't achieved. Homeowner checks stop strictly outside the boiler cover: inspect the exterior flue pipe termination for ice, snow, leaves, or bird nests and perform one manual reset. Never remove the combustion cover or bypass pressure switch contacts—a Gas Safe / certified SHK heating engineer* must inspect condensation-logged silicone tubes, venturi restrictions, fan RPM, differential Pa draft via manometer, and switch continuity ($150–$520 / €130–€450).

Safe to Operate?
No — Risk of Damage
DIY Difficulty
Professional Recommended
System
Air Pressure Switch & Flue
Professional Repair
$150 – $520

What This Fault Code Means

Before supplying gas to a fan-assisted Viessmann burner, the controller enforces a strict differential air-pressure check measured in Pascals (Pa). At idle, the switch must verify open state; during pre-purge, negative/positive venturi draft from the blower must snap its diaphragm closed. Moisture trapped inside tiny silicone sensing hoses, spider/soot obstructions at the venturi, or a stuck microswitch prevent that state transition and trigger F5.

Common Symptoms

  • Burner blower runs during purge without ever lighting a flame, then latches fault F5 / F05
  • Heating and hot water shut off completely—especially after windy rainstorms or freezing nights
  • Repeated clicking at the control relay before lockout

Most Likely Root Causes

  • Condensation droplets, kinks, or splits in the silicone air-pressure sensing tubes connected to the switch
  • Blocked exterior flue outlet (snow, ice, nesting debris) or strong back-pressure wind gusts
  • Defective differential air pressure switch (welded closed pre-purge or torn diaphragm failing to close)
  • Sluggish/dusty combustion fan failing to hit minimum Pa differential draft, or fouled venturi / wiring harness

Technical Thresholds & Specifications

Parameter / ConditionFactory Spec / Threshold
Sensed Safety Parameter

Measured at blower venturi taps before gas valve is energized

Differential Flue Pressure (Pa)
Pre/Post-Purge Switch Check

Stuck-closed pre-purge OR stuck-open post-purge triggers F5

Open pre-start -> Closed under fan Pa
Internal Service Boundary

Homeowners restricted to exterior flue check and single reset

Gas Safe / Certified SHK Engineer Only

Commonly Affected Models & Service Bulletins

  • Viessmann Vitopend 100-W & 200-W Fan-Assisted Gas Boilers
  • Viessmann Vitodens 100-W & 200-W Earlier Condensing Series (`F5` / `F05`)
  • Viessmann Vitogas / Fan-Flued Boilers with Differential Air Pressure Switch

Diagnostic Checks Before Replacing Parts

Verify the exact faulty component before ordering replacements.

  1. 1Homeowner safe check only: inspect the visible exterior boiler flue outlet for snow, icicles, leaves, or obstructions, and attempt one single manual Reset—never hammer resets repeatedly.
  2. 2Never open the boiler's room-sealed cabinet yourself; if F5 persists, isolate power cleanly and contact a certified heating engineer.
  3. 3Certified engineer diagnosis: examine silicone tubes for condensation/splits, measure live differential Pa pressure across fan taps with a digital manometer against Viessmann model data, test air switch microswitch continuity (open off / < 1 Ω running), and check fan wheel & venturi.

Interactive Symptom Triage

Answer 3 quick checks to narrow down the faulty component before spending money on parts.

Check 1 of 3

Was heavy snow/ice covering the external flue outlet and did one Reset restore stable firing?

Step-by-Step Troubleshooting & Fix

Tools & Parts Reference

Flashlight (homeowner exterior flue outlet visibility check only)Certified engineer: Digital Pa differential manometer & flue gas analyzerCertified engineer: OEM Viessmann air pressure switch, silicone tubes & multimeter
  1. 1Inspect accessible exterior flue terminal visually and clear any obvious external snow/leaves on outdoor grills without altering flue joints.
  2. 2Perform one single boiler Reset via selector/reset button.
  3. 3If F5 returns, power off the boiler and schedule a Gas Safe / certified SHK engineer immediately.
  4. 4The engineer drains moisture/replaces brittle silicone sensing hoses, clears venturi and flue passages, confirms differential draft in Pa meets factory spec, cleans/replaces the blower or swaps a faulty Viessmann air pressure switch.

Estimated Repair Cost Benchmark

Typical DIY parts and certified technician labor ranges. Select a currency below.

Currency:
Repair PathUSD
DIY Parts Only$0
Professional Repair (Parts + Labor)$150 – $520

Certified Technician Service Checklist

This fault involves sealed safety, gas, or high-voltage systems. Share these details when requesting a repair quote.

  • Share exact brand & fault code: Viessmann F5 (Air Pressure Switch & Flue)
  • Record appliance/boiler serial, model plate, or pressure reading before calling
  • Typical certified technician range: $150 – $520

Frequently Asked Questions

What is the difference between Viessmann F5 and F4?

F4 means flame ionization was not detected after attempting gas ignition, whereas F5 stops before gas even enters because the air pressure switch failed to prove safe combustion fan draft (Pa).

Why does Viessmann F5 happen frequently during cold winters?

Cold outdoor air chills the thin silicone pressure-sensing tubes connecting the fan venturi to the air pressure switch, condensing warm humid flue moisture into a tiny water droplet or ice plug that blocks Pa signal transfer.

Related Searches & Questions

Viessmann fault F5 air pressure switchViessmann Vitopend F05 error resetViessmann F5 silicone tubes Pa pressureViessmann boiler fault F5 repair cost

Verified Official & Engineering References

Plain Text / AI View

Related Fault Codes

HVAC & Boilers →
Viessmann Boiler Fault F5 (F05): Air Pressure… — Fixes & Cost | FaultCodes.org