# Viessmann F5: Viessmann Boiler Fault F5 (F05): Air Pressure Switch / Flue Draft Error

> **Quick Answer:** Fault code **F5** (also shown as **F05**) on Viessmann Vitopend and fan-flued Vitodens boilers indicates an **air pressure switch (`Prosestat` / *Differenzdruckwächter*) fault**: the switch either stayed stuck closed before fan startup or failed to close once the fan ran because differential pressure (**Pa**) wasn't achieved. Homeowner checks stop strictly outside the boiler cover: inspect the exterior flue pipe termination for ice, snow, leaves, or bird nests and perform **one manual reset**. Never remove the combustion cover or bypass pressure switch contacts—a **Gas Safe / certified SHK heating engineer** must inspect condensation-logged silicone tubes, venturi restrictions, fan RPM, differential Pa draft via manometer, and switch continuity ($150–$520 / €130–€450).

- **URL:** https://faultcodes.org/hvac/viessmann-f5
- **Category:** HVAC, Boilers & Heating
- **Brand / Standard:** Viessmann
- **System Area:** Air Pressure Switch & Flue
- **Severity:** Critical — Stop Immediately
- **Safe to Operate?:** No — Risk of Damage
- **DIY Difficulty:** Professional Recommended
- **Updated:** 2026-11-22T00:00:00Z

## What This Fault Code Means
Before supplying gas to a fan-assisted Viessmann burner, the controller enforces a strict differential air-pressure check measured in Pascals (`Pa`). At idle, the switch must verify open state; during pre-purge, negative/positive venturi draft from the blower must snap its diaphragm closed. Moisture trapped inside tiny silicone sensing hoses, spider/soot obstructions at the venturi, or a stuck microswitch prevent that state transition and trigger `F5`.

## Technical Thresholds & Specifications
| Parameter / Condition | Factory Spec / Threshold | Note |
| --- | --- | --- |
| Sensed Safety Parameter | Differential Flue Pressure (Pa) | Measured at blower venturi taps before gas valve is energized |
| Pre/Post-Purge Switch Check | Open pre-start -> Closed under fan Pa | Stuck-closed pre-purge OR stuck-open post-purge triggers F5 |
| Internal Service Boundary | Gas Safe / Certified SHK Engineer Only | Homeowners restricted to exterior flue check and single reset |

## Commonly Affected Models & Service Bulletins
- Viessmann Vitopend 100-W & 200-W Fan-Assisted Gas Boilers
- Viessmann Vitodens 100-W & 200-W Earlier Condensing Series (`F5` / `F05`)
- Viessmann Vitogas / Fan-Flued Boilers with Differential Air Pressure Switch

## Common Symptoms
- Burner blower runs during purge without ever lighting a flame, then latches fault `F5` / `F05`
- Heating and hot water shut off completely—especially after windy rainstorms or freezing nights
- Repeated clicking at the control relay before lockout

## Most Likely Root Causes
- Condensation droplets, kinks, or splits in the **silicone air-pressure sensing tubes** connected to the switch
- Blocked exterior **flue outlet** (snow, ice, nesting debris) or strong back-pressure wind gusts
- Defective **differential air pressure switch** (welded closed pre-purge or torn diaphragm failing to close)
- Sluggish/dusty **combustion fan** failing to hit minimum **Pa** differential draft, or fouled **venturi** / wiring harness

## Tools & Parts Reference
- Flashlight (homeowner exterior flue outlet visibility check only)
- Certified engineer: Digital Pa differential manometer & flue gas analyzer
- Certified engineer: OEM Viessmann air pressure switch, silicone tubes & multimeter

## Step-by-Step Troubleshooting & Fix
1. Inspect accessible exterior flue terminal visually and clear any obvious external snow/leaves on outdoor grills without altering flue joints.
2. Perform **one single boiler Reset** via selector/reset button.
3. If `F5` returns, power off the boiler and schedule a **Gas Safe / certified SHK engineer** immediately.
4. The engineer drains moisture/replaces brittle silicone sensing hoses, clears venturi and flue passages, confirms differential draft in **Pa** meets factory spec, cleans/replaces the blower or swaps a faulty **Viessmann air pressure switch**.

## Estimated Repair Cost Benchmark
| Currency | DIY Parts Only | Professional Repair (Parts + Labor) |
| --- | --- | --- |
| USD | $0–$0 | $150–$520 |
| GBP | £0–£0 | £100–£390 |
| CAD | CA$0–CA$0 | CA$190–CA$620 |
| EUR | €0–€0 | €130–€450 |
| CHF | CHF 0–CHF 0 | CHF 200–CHF 680 |

## Frequently Asked Questions
### What is the difference between Viessmann F5 and F4?
`F4` means flame ionization was not detected after attempting gas ignition, whereas `F5` stops *before* gas even enters because the air pressure switch failed to prove safe combustion fan draft (`Pa`).

### Why does Viessmann F5 happen frequently during cold winters?
Cold outdoor air chills the thin silicone pressure-sensing tubes connecting the fan venturi to the air pressure switch, condensing warm humid flue moisture into a tiny water droplet or ice plug that blocks `Pa` signal transfer.