# Vaillant F.22: Vaillant Boiler Fault Code F.22: Low System Water Pressure / Dry Fire

> **Quick Answer:** Vaillant fault code `F.22` (displayed as `F22`) means central heating water pressure dropped too low (**below `1.0 bar` cold**, locking out to prevent dry firing as pressure approaches `0.3–0.5 bar`). Check for radiator valve drips first, then repressurise slowly using Vaillant's external braided or built-in **filling loop** valves until the cold display reads **`1.0–1.5 bar`** (`1.2–1.5 bar` target), close BOTH filling taps firmly, and press Reset once. If pressure falls right back below `1.0 bar` over days/weeks—or spikes past `3.0 bar` when hot—have an engineer check a failing **expansion vessel**, weeping pressure relief valve (PRV), or hidden heating leak ($0 DIY repressurising; $120–$380 vessel recharge/PRV/sensor repair).

- **URL:** https://faultcodes.org/hvac/vaillant-f22
- **Category:** HVAC, Boilers & Heating
- **Brand / Standard:** Vaillant
- **System Area:** Boiler Water Pressure
- **Severity:** High — Service Soon
- **Safe to Operate?:** No — Risk of Damage
- **DIY Difficulty:** Easy (Basic Tools)
- **Updated:** 2026-11-22T00:00:00Z

## What This Fault Code Means
Vaillant ecoTEC boilers require hydraulic pressure (`1.0–1.5 bar` when cold) so hot water circulates smoothly across the stainless heat exchanger without boiling into steam pockets (`dry firing`). When pressure drops near `0.3–0.5 bar`—often after radiator bleeding, a tiny radiator valve weep, or a flat expansion vessel diaphragm discharging water out the external copper safety pipe—`F.22` halts the burner immediately.

## Technical Thresholds & Specifications
| Parameter / Condition | Factory Spec / Threshold | Note |
| --- | --- | --- |
| Normal Cold System Pressure | 1.0–1.5 bar (target ~1.2–1.5 bar) | Read on digital display or bottom gauge with heating completely cold |
| Dry-Fire Safety Lockout Zone | < 1.0 bar (locks out near ~0.3–0.5 bar) | Prevents overheating or steam pockets in primary heat exchanger |
| Hot Overpressure Danger Limit | >= 2.8–3.0 bar (PRV discharge threshold) | Swing from F.22 cold to >3 bar hot indicates deflated expansion vessel |
| Post-Fill Valve Verification | Firmly shut both filling loop valves | Prevents continuous over-pressurisation into closed heating circuit |

## Commonly Affected Models & Service Bulletins
- Vaillant ecoTEC plus & ecoTEC pro Gas Condensing Combi Boilers
- Vaillant ecoTEC sustain / pure / exclusive Series
- Vaillant ecoFIT & ecoCOMPACT Heating Units

## Common Symptoms
- Display flashes `F.22` with cold digital bar reading `0.0–0.6 bar` and zero heating or hot water
- Error occurred shortly after bleeding air from upstairs radiators
- Pressure cycles from `F.22` cold to `>3.0 bar` with outside copper pipe dripping when hot (flat expansion vessel)

## Most Likely Root Causes
- Recent **radiator bleeding** reducing closed-loop water volume without topping back up (most common harmless cause)
- Small weeping **radiator lockshield/TRV gland seal** or weeping boiler automatic air vent
- Deflated or ruptured **expansion vessel diaphragm** forcing excess pressure out the `3 bar` safety valve (`PRV`) when heated
- Blocked or failed Vaillant **water pressure sensor** reading false low pressure despite full radiators

## Tools & Parts Reference
- Built-in Vaillant filling taps or silver braided external filling loop key/hose
- Tissue paper (to inspect radiator valve tails for slow drips)
- Engineer pressure pump & calibrated gauge (only if recharging expansion vessel)

## Step-by-Step Troubleshooting & Fix
1. Ensure heating is cool, locate your Vaillant **filling loop** underneath the boiler (either two built-in integrated blue/grey taps or an external silver braided hose valve set).
2. Open BOTH filling valves slowly until water hisses gently into the system, watch the cold display climb smoothly to **`1.2–1.5 bar`** (stay strictly inside `1.0–1.5 bar` cold!), and then close BOTH valves firmly.
3. Press the Vaillant **Reset** button once; bleed trapped radiator air gently if gurgling appears and re-check pressure remains inside `1.0–1.5 bar`.
4. If pressure keeps dropping weekly without visible radiator drips—or climbs over `3 bar` when warm—book a certified heating engineer to recharge/replace the **expansion vessel**, clear the water pressure sensor port, or replace a dripping `3 bar` PRV.

## Estimated Repair Cost Benchmark
| Currency | DIY Parts Only | Professional Repair (Parts + Labor) |
| --- | --- | --- |
| USD | $0–$0 | $135–$420 |
| GBP | £0–£0 | £90–£320 |
| CAD | CA$0–CA$0 | CA$175–CA$540 |
| EUR | €0–€0 | €120–€380 |
| CHF | CHF 0–CHF 0 | CHF 175–CHF 490 |

## Frequently Asked Questions
### What should the water pressure be on a Vaillant ecoTEC boiler?
Cold operating pressure should sit strictly between **`1.0 and 1.5 bar`** (`1.2–1.5 bar` recommended target). Below `1.0 bar` risks `F.22` lockout (typically triggering around `0.3–0.5 bar`), while closing the filling valves tightly prevents climbing past `2.5–3.0 bar` hot.

### What if I leave the Vaillant filling loop taps open slightly by mistake?
Leaving filling valves open lets cold mains water keep filling the boiler past `3.0 bar`, blowing water outside through the safety discharge pipe—always verify both valves sit tightly shut perpendicular/closed afterward.