# Junkers / Bosch EA: Junkers / Bosch Boiler Fault EA: No Ionization Flame Detected After Ignition

> **Quick Answer:** Fault code **EA** on Junkers (Cerapur, Cerastar, Cerasmart) and Bosch Condens boilers means **no ionization flame was detected after the ignition sequence**: the boiler clicks and tries to ignite, yet fails to establish a stable flame signal (`> ~1.5–2 µA` DC). Safely verify whether there is any gas odor (if so, close the main gas valve, open windows, avoid electrical switches, and evacuate), confirm the appliance gas valve is open and another gas appliance works, thaw any frozen external plastic condensate pipe with **warm—never boiling—water**, and hold the **Reset / chimney-sweep reset button for ~3 seconds** (maximum 1–2 attempts). Never open the sealed combustion cover or adjust the gas valve—a **Gas Safe / certified DVGW heating engineer** must measure dynamic gas flow pressure (`~20 mbar`), clean/replace ignition and ionization electrodes, verify CO₂ combustion ratio, and clear internal condensate traps ($145–$540 / €125–€460).

- **URL:** https://faultcodes.org/hvac/junkers-ea
- **Category:** HVAC, Boilers & Heating
- **Brand / Standard:** Junkers / Bosch
- **System Area:** Flame Detection / Ignition
- **Severity:** Critical — Stop Immediately
- **Safe to Operate?:** No — Risk of Damage
- **DIY Difficulty:** Professional Recommended
- **Updated:** 2026-11-23T00:00:00Z

## What This Fault Code Means
During every startup on Heatronic III / IV or Bosch BC20/UI300 controls, the fan pre-purges, the ignition transformer arcs across the spark electrode, and the gas combination valve opens for a short safety window (`~3–5 s`). Combustion plasma must immediately rectify AC probe voltage into a continuous DC microampere signal (`≥ 2 µA`, typically `4–10 µA`) on the ionization electrode. Lack of gas, backed-up condensate drowning the burner, fouled ceramic probes, reversed electrical polarity (`L/N`), or a faulty gas valve causes `EA` lockout.

## Technical Thresholds & Specifications
| Parameter / Condition | Factory Spec / Threshold | Note |
| --- | --- | --- |
| Ionization Detection Minimum | ≥ ~1.5–2.0 µA DC (Normal run ~4–10 µA) | Evaluated across ~3–5 s ignition safety time on Heatronic / Bosch controllers |
| Natural Gas Flow Pressure | 20 mbar nominal (17–25 mbar E/LL; 50 mbar LPG) | Significant drop during burner start starves ignition and causes EA |
| Reset Procedure | Hold Reset ~3 seconds (max 1–2 attempts) | Repeated resets without gas/condensate checks risk unburnt gas buildup |
| Safety & Access Standard | Gas Safe / Certified DVGW Engineer Only | Gas valve calibration and electrode replacement require flue gas analyzer |

## Commonly Affected Models & Service Bulletins
- Junkers Cerapur / CerapurComfort / CerapurSmart / CerapurAcu (ZSB, ZWB, ZWBR Series)
- Junkers Cerastar / Ceraclass / Ceramini Gas Wall-Hung Boilers
- Bosch Condens 2000W / 3000W / 5000W / 7000iW / 9000iW Series

## Common Symptoms
- Display flashes `EA` (often with red warning LED) and neither heating nor domestic hot water runs
- Rapid spark clicking heard inside the boiler for 3–5 seconds followed by quiet shutdown
- Commonly appears during sub-zero winter nights (frozen external condensate drain) or after gas meter/pipe maintenance

## Most Likely Root Causes
- Interrupted gas supply, closed appliance/meter gas valve, air pocket in newly serviced gas pipe, or **failed gas pressure regulator**
- Frozen external **condensate discharge pipe** or choked internal condensate trap backing water into the combustion chamber
- Worn, carbon-fouled, bent, or cracked **ignition / ionization electrode assembly** or damaged HT spark lead
- Sticking **gas combination valve**, improper **CO₂ air-gas ratio**, blocked concentric flue exhaust recirculation, or faulty **Heatronic ignition PCB**

## Tools & Parts Reference
- Warm (never boiling) water only for thawing exterior plastic condensate lines
- Certified engineer: Digital gas manometer (mbar), µA multimeter & flue gas analyzer (CO/CO₂)
- Certified engineer: OEM Junkers/Bosch ignition & ionization electrode kit + gaskets

## Step-by-Step Troubleshooting & Fix
1. Verify gas supply availability (open gas valve, active gas meter credit/flow) and rule out any smell of gas.
2. If sub-zero weather froze an outside plastic condensate pipe, slowly pour **warm (never boiling)** water over the exterior pipe elbow until the ice plug clears.
3. Hold the **Reset button for ~3 seconds** (maximum 1–2 times); if `EA` returns, switch off the boiler electrical spur and do not force further resets.
4. Call a **Gas Safe / certified SHK heating engineer** to flush the internal condensate trap, clean or replace **ignition and ionization electrodes**, verify dynamic gas flow pressure and **gas combination valve** modulation, and calibrate CO₂ combustion values.

## Estimated Repair Cost Benchmark
| Currency | DIY Parts Only | Professional Repair (Parts + Labor) |
| --- | --- | --- |
| USD | $0–$0 | $145–$540 |
| GBP | £0–£0 | £95–£410 |
| CAD | CA$0–CA$0 | CA$190–CA$660 |
| EUR | €0–€0 | €125–€460 |
| CHF | CHF 0–CHF 0 | CHF 195–CHF 670 |

## Frequently Asked Questions
### How do you properly reset Junkers / Bosch fault EA?
First verify gas is available and external condensate lines aren't frozen, then press and hold the **Reset button for about 3 seconds** (1–2 tries maximum). Never bypass safeties or repeatedly hammer Reset if `EA` returns.

### Why does Junkers EA happen suddenly during freezing winter weather?
Condensing boilers discharge acidic condensate water; if an exposed outdoor drain pipe freezes solid, condensate backs up inside the combustion chamber, drowning the burner and spark electrodes and causing immediate `EA` lockout.


## Verified Official & Engineering References
- [Bosch Home Comfort: Störungscodes & Service-Hilfe](https://www.bosch-homecomfort.com/de/de/wohngebaeude/service/stoerungscodes/) (Official Support)
- [Bosch Home Comfort Global Portal](https://www.bosch-homecomfort.com/) (Official Support)
- [DVGW Technische Regeln für Gasinstallationen (TRGI)](https://www.dvgw.de/) (Regulation / Standard)